All bored and notched service locations are found
Critical itemProtection can only be verified after every cable, raceway, pipe, and tubing run through wood framing is visible. Late trade work and re-drilled holes must be included before cover-up.
A US pre-drywall check for nail plates, stud guards, and shield plates where cables, raceways, and pipes pass through bored or notched wood framing.
7 items to check
These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.
If you notice an error, please email [email protected].
For a complete inspection, also consider:
Broader open-wall rough-in checks that should be completed before this focused nail-plate pass.
Adjacent top-plate inspection for sealing service penetrations after protection plates and supports are confirmed.
Protection can only be verified after every cable, raceway, pipe, and tubing run through wood framing is visible. Late trade work and re-drilled holes must be included before cover-up.
NEC 300.4 requires wiring methods through wood members to be protected where the required distance from the wood face cannot be maintained. Common NEC language uses a 1-1/4 inch setback and steel plate or bushing protection at least 1/16 inch thick when that setback is not available.
IRC P2603.2.1 and adopted IPC or UPC provisions require steel shield plates where protected piping is too close to framing faces in concealed locations. The exact distance, plate thickness, and extension rules can vary by adopted edition and local amendment, so verify the project code and AHJ.
A nail plate or shield plate should protect the side of the framing member where nails, screws, trim fasteners, cabinet screws, or future wall attachments can enter. One plate on one face may not protect a service close to the opposite face.
Fastener protection does not repair over-bored studs, over-notched studs, cut engineered members, or top plates cut beyond IRC limits. IRC R602.6 and R602.6.1, approved stud shoes, engineered details, manufacturer instructions, and AHJ approval control structural repairs.
Protection plates should be firmly seated, sized for the vulnerable area, and installed without piercing, crushing, kinking, or abrading the cable, raceway, or pipe they protect. Use listed or approved products where the adopted code or manufacturer requires them.
Pre-drywall protection should be documented before insulation, fireblocking touch-ups, and drywall hide the work. Any service added after inspection must be rechecked for nail plates, shield plates, support, and fireblocking.
Use this checklist after electrical, low-voltage, plumbing, and mechanical rough-ins are in place, but before insulation and drywall conceal the framing. Focus on bored or notched studs, top plates, and bottom or sole plates where finish fasteners could reach concealed cables, raceways, or piping. Compare the work with the adopted NEC, IRC, IPC or UPC, approved plans, manufacturer instructions, local amendments, and the AHJ.
A US-focused open-wall checklist for residential framing, fireblocking, rough openings, and trade rough-ins before drywall.
A US pre-drywall check for sealing top-plate and ceiling-line service penetrations so concealed wall cavities are cut off before insulation and drywall.