Skip to content

Electrical Installation Inspection

Checklists for inspecting electrical installations in accordance with CEI 64-8, CEI 64-50, EN 61439, D.M. 37/2008 and Italian safety regulations for residential and commercial buildings.

7 items to check

BETA

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email [email protected].

Inspection progress0 of 7
0%

Distribution board

Critical item

Per EN 61439-3, domestic and similar consumer units must be type-tested or verified assemblies. All socket-outlet circuits must be protected by 30 mA RCDs per HD 60364-4-41. Circuit breakers must comply with EN 60898 or EN 61009 (RCBOs). Each circuit must be clearly labelled with its designation and protective device rating.

Cable installation

Critical item

Per HD 60364-5-52, cables must be selected and installed according to the installation method, ambient temperature, and grouping. Cable sizing must account for voltage drop (max 3–5 % per HD 60364-5-52 Annex G), current-carrying capacity, and fault current. Fire performance of cables must meet EN 13501-6 classification where required. Cable support and fixings must comply with HD 60364-5-52 requirements for spacing and methods.

Socket outlets and switches

Socket outlets must comply with EN 60309 for industrial applications or national standards for domestic types. Installation heights must meet accessibility requirements. In wet areas per HD 60364-7-701, minimum IP ratings apply (IPX4 in Zone 2). All accessories must be correctly fixed, and conductor terminations must be secure with no exposed live parts.

Lighting circuits

Workplace lighting must meet minimum maintained illuminance levels per EN 12464-1 (e.g. 500 lux for offices, 300 lux for circulation areas). Outdoor workplace lighting per EN 12464-2. Emergency escape lighting must comply with EN 1838, with minimum 1 lux along escape routes and 0.5 lux in open areas. Emergency luminaires must be tested per EN 50172.

Earthing and bonding

Critical item

Per HD 60364-5-54, the earthing arrangement (TN-S, TN-C-S, or TT) must be correctly implemented with appropriate earth electrode resistance for TT systems. Main equipotential bonding must connect incoming services (water, gas, structural steel) per HD 60364-4-41. Supplementary equipotential bonding is required in special locations such as bathrooms per HD 60364-7-701. Earth conductor sizing must comply with HD 60364-5-54 Table 54.1.

Special locations (bathrooms)

Critical item

Per HD 60364-7-701, bathrooms are divided into Zones 0, 1, and 2 with specific requirements for each. Zone 0 (inside bath/shower): only SELV at 12 V AC or 30 V DC. Zone 1 (above bath to 2.25 m): minimum IPX4, only fixed equipment with suitable IP rating. Zone 2 (0.6 m from Zone 1): minimum IPX4, socket outlets permitted only with 30 mA RCD and SELV shavers supply per EN 61558-2-5.

Testing and certification

Critical item

Per HD 60364-6, all new installations and alterations must be verified by inspection and testing before being put into service. Required tests include continuity of protective conductors, insulation resistance (minimum 1 MΩ at 500 V DC for LV circuits), earth fault loop impedance, RCD operation (within 40 ms at 5×IΔn for Type AC), and prospective fault current. Results must be recorded on appropriate certification documents.