Roof structure verification
Critical itemPer EN 1991-1-1, permanent loads (self-weight of roofing, battens, insulation) must be accurately determined. Snow loads must be calculated per EN 1991-1-3 using the characteristic ground snow load for the site location and roof shape coefficients. Wind loads per EN 1991-1-4 must account for uplift on the roof covering, including higher local pressures at edges and corners. The structure must be designed to Eurocodes EN 1993 (steel), EN 1995 (timber), or EN 1992 (concrete).