Plumbing and Sanitary Installation Inspection

Checklist for inspecting plumbing and sanitary installations in accordance with DTU 60.1 (water supply), DTU 60.32 (drainage), NF EN 806-4 (commissioning), and NF EN 1717 (backflow protection).

7 items to check

BETA

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email [email protected].

Inspection progress0 of 7
0%

Water Supply Installation

Critical item

Per DTU 60.1 (NF P 40-201), water supply installations must use approved materials (copper per NF EN 1057, PER/PEX per NF EN ISO 15875, or multilayer per NF EN ISO 21003) with proper sizing per DTU 60.11. Pipes must be routed to avoid freezing, properly supported at specified intervals, and equipped with isolation valves at each branch and appliance.

Drainage and Waste Water Systems

Critical item

Per DTU 60.32 (NF P 41-213), drainage installations must be designed to convey waste water efficiently with minimum gradients of 1% for horizontal runs (3% preferred for branch connections). All waste pipes must be vented to prevent siphoning of traps. Pipe materials must comply with NF EN 1329 (PVC-U) or NF EN 1451 (PP). Traps must maintain a minimum water seal of 50 mm.

Hot Water Production and Legionella Prevention

Critical item

Per French regulation (Arrêté du 30 novembre 2005) and DTU 60.1, hot water systems must be designed to prevent Legionella proliferation. Storage water heaters must maintain water at a minimum of 55°C (60°C recommended) at the base of the tank. Distribution must deliver water at 50°C minimum at the furthest point within 30 seconds for systems exceeding 3 litres of dead leg volume. A recirculation loop is mandatory for buildings where the volume between the production point and the furthest draw-off exceeds 3 litres.

Pipe Support, Insulation, and Routing

Per DTU 60.1, pipes must be supported at specified intervals depending on material and diameter. Hot water pipes and pipes in unheated spaces must be insulated per RE 2020 energy requirements. Pipe routing must allow for thermal expansion and avoid contact between incompatible materials.

Pressure Testing and Commissioning

Critical item

Per NF EN 806-4 (commissioning of water installations) and DTU 60.1, all water supply pipework must be pressure tested before concealment and before commissioning. The test pressure must be at least 1.5 times the maximum operating pressure, with a minimum of 10 bar, maintained for a minimum duration without pressure drop. Drainage systems must be tested for watertightness per DTU 60.32.

Backflow Prevention and Potable Water Protection

Critical item

Per NF EN 1717, potable water supplies must be protected against backflow contamination by installing appropriate backflow prevention devices matched to the fluid category risk. Each connection point must be assessed for the contamination risk level (categories 1-5), and the correct type of backflow preventer installed. DTU 60.1 requires a type EA disconnector (controllable backflow preventer) at the building entry for collective installations.

Gas Installation

Critical item

Per DTU 61.1 (NF P 45-204), gas installations must comply with strict requirements for pipe materials, routing, ventilation, and safety devices. Copper (NF EN 1057) or steel (NF EN 10255) pipes are used internally, with PE pipes (NF EN 1555) for buried external runs. All gas installations require a tightness test before commissioning and must be certified by a Qualigaz-accredited inspector. Ventilation openings must be provided per DTU 61.1 for combustion air supply.

Checklist for inspecting plumbing and sanitary installations in accordance with DTU 60.1 (water supply), DTU 60.32 (drainage), NF EN 806-4 (commissioning), and NF EN 1717 (backflow protection).

Reference Standards

  • DTU 60.1 (NF P 40-201) — Water supply plumbing
  • DTU 60.32 (NF P 41-213) — Drainage and waste water
  • DTU 60.11 — Rules for calculating water supply installations
  • NF EN 806-4 — Specifications for installations inside buildings conveying water for human consumption — commissioning
  • NF EN 1717 — Protection against pollution of potable water
  • DTU 61.1 (NF P 45-204) — Gas installations
  • RE 2020 — Environmental regulation for pipe insulation
  • Required Tools

  • Pressure gauge and test pump
  • Pipe level and laser level
  • Thermometer (contact and infrared)
  • Flow meter
  • Smoke pellets or drain camera