Skip to content

Electrical Installation Inspection

Checklist for inspecting electrical installations in accordance with NF C 15-100 (low-voltage installation rules) and the requirement for Consuel certification before energisation.

7 items to check

BETA

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email [email protected].

Inspection progress0 of 7
0%

Electrical Distribution Board

Critical item

Per NF C 15-100, the distribution board (tableau électrique) must be installed in a dedicated Gaine Technique Logement (GTL) accessible from the main living area. The board must include a main switch (disjoncteur de branchement), residual current devices (RCDs) covering all circuits, and individual circuit breakers sized to the cable cross-section. A minimum of 20% spare capacity must be provided for future circuits. The board must be installed between 1.0 m and 1.8 m height for the operating handles.

Cabling and Wiring Systems

Critical item

Per NF C 15-100 and UTE C 15-520, cables must be selected and installed according to the circuit type, installation method, and environmental conditions. Minimum cable cross-sections are specified: 1.5 mm² for lighting circuits, 2.5 mm² for socket circuits, and 6 mm² for dedicated appliance circuits (cooker, electric heating). Cables must be protected against mechanical damage, and the colour code must follow the harmonised standard: blue for neutral, green/yellow for earth, and brown/black/grey for live conductors.

Socket Outlets — Minimum Provision per Room

Per NF C 15-100 (Amendment A5), each room type has a specified minimum number of socket outlets. Living rooms require a minimum of 5 sockets (7 if over 28 m²), bedrooms require 3, kitchens require 6 (including 4 above the worktop), and hallways/corridors require 1 per 4 m². All socket outlets must be of the French type E (with earth pin) and protected by 30 mA RCDs. Maximum 8 sockets per 20 A circuit using 2.5 mm² cable.

Lighting Circuits and Points

Per NF C 15-100, each room must have at least one ceiling-mounted lighting point controlled by a wall switch at the room entrance. A maximum of 8 lighting points are permitted per 16 A circuit using 1.5 mm² cable. Switches must be installed between 0.90 m and 1.30 m above finished floor level. Two-way switching (va-et-vient) is required for rooms with multiple entrances and for corridors. Exterior lighting must be on a dedicated circuit protected by a 30 mA RCD.

Earthing and Equipotential Bonding

Critical item

Per NF C 15-100, the installation must have a main earth terminal connected to the earth electrode (typically a foundation earth per NF C 15-100 section 542). The earth resistance must be compatible with the protective device settings to ensure disconnection within the required time (0.4 s for socket circuits, 5 s for distribution circuits). Supplementary equipotential bonding is required in bathrooms, connecting all exposed and extraneous conductive parts. The main equipotential bonding must connect all metallic services entering the building.

Bathroom Electrical Zones

Critical item

Per NF C 15-100 section 701, bathrooms are divided into protective zones (0, 1, 2, and volume hors volume) that restrict which electrical equipment may be installed and at what IP rating. Zone 0 is inside the bath/shower tray; Zone 1 extends to 2.25 m above the bath/shower floor; Zone 2 extends 0.60 m beyond Zone 1. All circuits supplying bathroom equipment must be protected by a 30 mA RCD. Only SELV (12 V) equipment is permitted in Zone 0, and equipment in Zones 1 and 2 must meet minimum IPX4/IPX5 ratings.

Consuel Certification

Critical item

Per French regulation, all new electrical installations and major renovations must obtain a certificate of conformity (attestation de conformité) from the Comité National pour la Sécurité des Usagers de l'Électricité (Consuel) before the electricity distributor (Enedis) will energise the supply. The installer completes a self-declaration of conformity, which is then verified by a Consuel inspector. The inspection covers compliance with NF C 15-100 for the complete installation. Without the Consuel visa, the electricity supply connection will be refused.

Checklist for inspecting electrical installations in accordance with NF C 15-100 (low-voltage installation rules) and the requirement for Consuel certification before energisation.

Reference Standards

  • NF C 15-100 — Low-voltage electrical installations in buildings
  • NF C 14-100 — Service connection installations
  • NF C 15-100 Amendment A5 — Residential installations (updated room-by-room requirements)
  • UTE C 15-520 — Wiring systems and cable selection
  • NF EN 60898 — Circuit breakers for overcurrent protection
  • NF EN 61008/61009 — Residual current devices (RCDs)
  • Required Tools

  • Multifunction installation tester (insulation, loop impedance, RCD)
  • Voltage tester (two-pole)
  • Socket tester with RCD trip function
  • Thermal imaging camera
  • Lux meter