Waterproofing Inspection

Checklist for inspecting waterproofing systems in accordance with DTU 14.1 (below-grade waterproofing), DTU 43.1 (roof waterproofing), and EN 14967 (flexible sheets for waterproofing).

6 items to check

BETA

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email [email protected].

Inspection progress0 of 6
0%

Substrate Preparation and Condition

Critical item

Per DTU 14.1 and DTU 43.1, the substrate must be clean, dry, smooth, and free from defects before waterproofing application. Surface moisture content must not exceed the limits specified for the chosen membrane system. EN 13967 specifies substrate requirements for moisture barrier installations.

Membrane Installation and Overlap Integrity

Critical item

DTU 14.1 and DTU 43.1 specify minimum overlap widths, bonding methods, and installation sequences for waterproofing membranes. EN 14967 defines performance requirements for flexible sheet membranes. All laps must be fully sealed with no voids, wrinkles, or fish-mouths.

Detail Connections and Penetrations

Critical item

Per DTU 14.1 and DTU 43.1, all junctions between waterproofing membranes and building elements (walls, pipes, drains) must be sealed with dedicated detail components. Upstand heights, corner treatments, and collar details must comply with the DTU minimum dimensions.

Protection and Drainage Layers

DTU 14.1 requires that below-grade waterproofing be protected from mechanical damage by a protection board or geotextile drainage layer. DTU 43.1 specifies protection layers for roof membranes including gravel ballast, paving, or green roof substrates. EN 13252 covers geotextile drainage composites.

Water Tightness Testing and Verification

Critical item

DTU 14.1 and DTU 43.1 require flood testing or spray testing of completed waterproofing systems before concealment. Flat roofs must be flood-tested to a minimum depth of 50 mm for 48 hours per DTU 43.1. Below-grade systems must be inspected before backfill.

Warranty and As-Built Documentation

Per DTU 14.1 and DTU 43.1, the waterproofing contractor must provide complete as-built documentation including membrane product certificates, test reports, and warranty conditions. French decennial liability (garantie decennale) applies to waterproofing as it is considered a structural element under French building law.

Checklist for inspecting waterproofing systems in accordance with DTU 14.1 (below-grade waterproofing), DTU 43.1 (roof waterproofing), and EN 14967 (flexible sheets for waterproofing).

Reference Standards

  • DTU 14.1 (NF P 11-221) — Waterproofing of below-grade structures
  • DTU 43.1 (NF P 84-204) — Roof waterproofing with bituminous membranes
  • EN 14967 — Flexible sheets for waterproofing
  • EN 13967 — Flexible sheets for waterproofing — Moisture barriers
  • DTU 20.1 — Masonry walls: waterproofing requirements
  • Required Tools

  • Moisture meter
  • Infrared thermography camera
  • Spray test equipment
  • Tape measure and spirit level
  • Adhesion tester