Skip to content

EV Charger Installation Inspection

Checklist for inspecting electric vehicle (EV) charger (EVSE) installation per applicable national electrical code.

7 items to check

BETA

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email [email protected].

Inspection progress0 of 7
0%

Electrical capacity assessment

Critical item

Per REBT 625.40 and NEC 220, the existing electrical service must have sufficient capacity for the EV charger load. A Level 2 charger typically draws 30–50A continuously (7.2–12 kW). Per REBT 625.42, the circuit must be rated at 125% of the continuous load. A 200A panel is recommended; 100A panels may require a load management system.

Charger selection

Per REBT 625.44, EV supply equipment must be listed and labeled. Level 1 (230V, 12A) uses standard outlet. Level 2 (400V, 16–48A) is the most common home install. Hardwired units must be installed per manufacturer instructions. Plug-in units use NEMA 14-50 or 6-50 receptacles. Charger must be rated for outdoor/indoor use as appropriate (NEMA 3R minimum outdoor).

Dedicated circuit installation

Critical item

Per REBT 625.40, each EV charger requires a dedicated branch circuit. Wire sizing per REBT (RD 842/2002) 310.16: 6 AWG copper for 50A, 4 AWG copper for 60A. Conduit required per local code (EMT, PVC, or flexible). Circuit must be continuous from panel to charger with no taps. For 48A EVSE, a 60A breaker with 6 AWG wire is the NEC minimum.

Mounting and placement

Per REBT 625.44 and manufacturer instructions, EV chargers must be mounted securely at an accessible height (typically 42–48 inches to connector holder). Wall-mounted units require proper anchoring to studs or masonry. Pedestal-mounted units require a concrete base. Cable management must keep the charging cable off the ground when not in use.

RCD (diferencial) and personnel protection

Critical item

Per REBT 625.54, all EV charger outlets installed in garages must have RCD (diferencial) protection. Most listed EVSE units include built-in ground fault protection per AENOR 2231. Plug-in chargers using NEMA 14-50 receptacles in garages require a RCD (diferencial)-protected circuit. For outdoor installations, RCD (diferencial) is required per REBT (RD 842/2002) 210.8.

Permit and inspection

Critical item

Per REBT 80.19 and local building codes, EV charger installation on a new dedicated circuit requires an electrical permit in most jurisdictions. The installation must be inspected and approved by the local AHJ. Some utilities require notification for loads over 40A. Many jurisdictions have streamlined EV permitting to encourage adoption.

Testing and commissioning

Critical item

Per REBT 625 and manufacturer instructions, the installed EVSE must be tested before regular use. Verify correct voltage, amperage draw matches charger rating, ground fault protection operates, and vehicle charges successfully. Wi-Fi connectivity and scheduling features should be configured and tested.

Checklist for inspecting electric vehicle (EV) charger (EVSE) installation per applicable national electrical code.

Reference Standards

  • REBT (RD 842/2002) Article 625 — Electric Vehicle Charging Systems
  • UL 2594 — EV Supply Equipment
  • UL 2231 — Personnel protection for EV supply circuits
  • SAE J1772 — EV connector standard (Level 1 & 2)
  • Tools Needed

  • Multimeter
  • Clamp ammeter
  • Non-contact voltage tester
  • Torque screwdriver
  • Level
  • Tape measure