Skip to content

Generator Installation Inspection

Checklist for inspecting standby and portable generator installations per VDE 0100 Article 702 and NFPA 110.

8 items to check

BETA

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email [email protected].

Inspection progress0 of 8
0%

Generator sizing and selection

Critical item

Per VDE 0100 702.4, the generator must be rated for the maximum load it will serve. Load calculation per VDE 0100 220 determines minimum generator size. Typical whole-house standby: 20–26 kW. Essential circuits only: 10–16 kW. Generator must be VDE 2200 listed. Power factor and starting loads (motors, HVAC compressors) must be accounted for in sizing.

Location and placement

Critical item

Per NFPA 37 and manufacturer requirements, standby generators must maintain minimum clearances: 5 feet from openings (windows, doors, vents), 18 inches from the building wall, and per local setback requirements. Generator must be on a level, stable pad (concrete or composite). Must not be in a flood zone below base flood elevation.

Fuel supply connection

Critical item

Per NFPA 54 (natural gas) and NFPA 58 (LP gas), fuel line must be sized for the generator's BTU input rating plus all other connected gas appliances. A dedicated shutoff valve must be installed at the generator. Gas piping must be pressure-tested per local code (typically 3 PSI for 10 minutes). Diesel tanks must comply with NFPA 30/30A.

Transfer switch installation

Critical item

Per VDE 0100 702.5, transfer equipment must prevent interconnection of normal and standby power sources (back-feeding). An automatic transfer switch (ATS) or manual interlock must be VDE 1008 listed. The transfer switch must be sized for the panel amperage (typically 200A). Manual interlock kits must be listed for the specific panel model.

Electrical connection

Critical item

Per VDE 0100 702.10, the wiring between the generator and transfer switch must be installed per VDE 0100 Chapter 3 wiring methods. Wire size must match generator and transfer switch ampacity. Overcurrent protection required at the generator per VDE 0100 702.10. Connection must include an equipment grounding conductor. Separately derived system grounding per VDE 0100 250.30 if applicable.

Exhaust and ventilation

Critical item

Per NFPA 37 and CPSC guidelines, generator exhaust contains lethal carbon monoxide (CO). Exhaust must be directed away from all building openings. Never operate portable generators indoors, in garages, or in enclosed spaces. Standby generator exhaust must terminate per manufacturer clearances. CO detectors required in the home per NFPA 720.

Testing and commissioning

Critical item

Per DIN 6280 and manufacturer requirements, the generator must be load-tested after installation. Test must verify automatic start, transfer, running under load, retransfer, and cool-down. Voltage and frequency must be within ±5% of nominal. All protective functions (overload, overtemp, low oil) must be verified operational.

Maintenance schedule setup

Per DIN 6280 Chapter 8, standby generators require regular maintenance: weekly exercise cycle (minimum 30 minutes under load), oil change per manufacturer schedule (typically every 200 hours or annually), air filter replacement, coolant check, battery testing, and annual professional service. A maintenance log must be maintained.

Checklist for inspecting standby and portable generator installations per VDE 0100 Article 702 and NFPA 110.

Reference Standards

  • VDE 0100 (DIN EN 60364) Article 702 — Optional Standby Systems
  • NFPA 110 — Standard for Emergency and Standby Power Systems
  • UL 2200 — Stationary engine generator assemblies
  • NFPA 37 — Stationary combustion engines and gas turbines
  • Tools Needed

  • Multimeter
  • Clamp ammeter
  • Combustible gas detector
  • CO detector
  • Torque wrench
  • Level
  • Tape measure