Skip to content

Electrical Installation

Checklist for inspecting electrical installations in accordance with DIN VDE 0100 series and DIN 18015.

7 items to check

BETA

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email [email protected].

Inspection progress0 of 7
0%

Distribution Board (DIN VDE 0100-410)

Critical item

The main distribution board and sub-distribution boards must comply with DIN VDE 0100-410 for protection against electric shock and DIN VDE 0603-1 for consumer units. Each final circuit must be protected by an appropriate overcurrent protective device (MCB) rated for the cable cross-section and expected load. Residual current devices (RCDs) with a rated residual current of 30 mA must protect all socket-outlet circuits per DIN VDE 0100-410. Type A RCDs are the minimum requirement; Type B RCDs are required for circuits supplying equipment with DC fault current components (e.g. EV chargers, inverters). Selective RCDs (Type S, time-delayed) should be used upstream to prevent nuisance tripping of the entire installation. A minimum of 20% spare capacity must be provided for future circuit additions.

Cable Installation (DIN VDE 0100-520 / DIN 18015-1)

Critical item

Cable selection and installation must comply with DIN VDE 0100-520 and DIN 18015-1. Cable types must be appropriate for the installation method and environment — NYM-J for fixed installation in dry and damp locations, NYY-J for underground and outdoor runs. Cable cross-sections must be calculated for current-carrying capacity, voltage drop (maximum 3% for lighting, 5% for other circuits per DIN 18015-1) and short-circuit withstand. Installation zones for concealed wiring in walls must follow DIN 18015-3 — vertical zones of 200 mm width adjacent to door frames, window frames and room corners, and horizontal zones at 150 mm and 300 mm from the finished floor and 150 mm from the finished ceiling. Cables outside these zones require mechanical protection or documentation.

Sockets and Switches (DIN 18015-2)

The type and minimum number of socket-outlets and lighting connections must comply with DIN 18015-2. The standard defines three equipment levels: minimum (1), standard (2) and comfort (3). For equipment level 2 (standard residential), the minimum requirements include: living rooms — 5 socket-outlets; bedrooms — 3 socket-outlets; kitchen — 6 socket-outlets including dedicated circuits for oven and hob; bathroom — 2 socket-outlets (outside zones 0-2); hallway — 1 socket-outlet per 4 m length. Each room must have at least one switched lighting connection point. Socket-outlets must be Schuko type (CEE 7/3) rated at 16 A, installed at a standard height of 300 mm above finished floor level or 1050 mm for worktop-level outlets.

Lighting Installation (DIN EN 12464-1)

Interior lighting must comply with DIN EN 12464-1 for workplaces and DIN 5035 for general lighting design. The standard specifies minimum maintained illuminance levels by room type and task — offices require 500 lux at desk level, corridors 100 lux, stairways 150 lux and residential living areas typically 200 lux. Uniformity of illuminance (Uo) must be at least 0.6 in task areas. Glare must be controlled — the Unified Glare Rating (UGR) must not exceed the specified limit for the room type (e.g. UGR ≤ 19 for offices). Emergency lighting must comply with DIN EN 1838 with a minimum of 1 lux on escape routes. Light fitting positions must be coordinated with ceiling systems and other services.

Earthing and Protective Conductors (DIN VDE 0100-540)

Critical item

Earthing arrangements and protective conductors must comply with DIN VDE 0100-540. The earthing system type (TN-S, TN-C-S or TT) must be identified and all protective conductors correctly connected. The main earthing terminal (Haupterdungsschiene) must bond together the earthing conductor, protective conductors, equipotential bonding conductors and functional earthing conductors. Supplementary equipotential bonding per DIN VDE 0100-410 must connect all simultaneously accessible exposed-conductive-parts and extraneous-conductive-parts in locations of increased risk (bathrooms, swimming pools). The earth electrode resistance must be measured and documented. Protective conductor cross-sections must comply with DIN VDE 0100-540 Table 54.2.

Bathroom Electrical Installations (DIN VDE 0100-701)

Critical item

Electrical installations in bathrooms and shower rooms must comply with DIN VDE 0100-701, which defines protection zones and permitted equipment for each zone. Zone 0 (inside the bath or shower tray): only SELV at maximum 12 V AC. Zone 1 (above the bath/shower to 2.25 m height): only fixed equipment rated minimum IPX4, supplied via SELV or protected by 30 mA RCD. Zone 2 (0.6 m from Zone 1 boundary): fixed equipment rated minimum IPX4, protected by 30 mA RCD. Outside zones: all circuits must be protected by 30 mA RCD. Socket-outlets are only permitted outside Zone 2 (minimum 0.6 m from the Zone 1 boundary) or via SELV transformer. Supplementary equipotential bonding per DIN VDE 0100-701 Section 701.415.2 must connect all exposed and extraneous conductive parts.

Testing and Verification (DIN VDE 0100-600)

Critical item

Initial verification of the completed electrical installation must comply with DIN VDE 0100-600. The verification comprises visual inspection and testing, carried out by a qualified electrician before the installation is energised and handed over. Required tests include: continuity of protective conductors and equipotential bonding (maximum 1 Ω), insulation resistance (minimum 1 MΩ at 500 V DC for SELV/PELV circuits, minimum 0.5 MΩ for other circuits up to 500 V), earth electrode resistance, RCD operation (trip time and trip current), loop impedance (Zs) to verify disconnection times, and polarity verification. All test results must be recorded on a standardised test certificate (Prüfprotokoll) and handed to the building owner.

Checklist for inspecting electrical installations in accordance with DIN VDE 0100 series and DIN 18015.

Reference Standards

  • DIN VDE 0100-410 — Protection against electric shock
  • DIN VDE 0100-520 — Selection and erection of wiring systems
  • DIN VDE 0100-540 — Selection and erection of electrical equipment: Earthing and protective conductors
  • DIN VDE 0100-600 — Verification (initial inspection and testing)
  • DIN VDE 0100-701 — Requirements for special installations: Bathrooms
  • DIN 18015-1 — Electrical installations in residential buildings: Planning principles
  • DIN 18015-2 — Electrical installations in residential buildings: Type and minimum number of socket-outlets and lighting connections
  • Required Tools

  • Multifunction installation tester (insulation, loop impedance, RCD)
  • Voltage indicator (two-pole)
  • Clamp meter
  • Lux meter
  • Wiring and circuit documentation