Skip to content

Fire Resistance Inspection

Checklist for inspecting fire resistance ratings of building assemblies per NBC Part 3 (Fire Protection, Occupant Safety and Accessibility) and ULC (Underwriters Laboratories of Canada) standards.

7 items to check

BETA

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email [email protected].

Inspection progress0 of 7
0%

Fire separation ratings

Critical item

Per NBC 3.1.7 and 3.2.1, fire separations must achieve the fire-resistance rating shown on the drawings, as determined by CAN/ULC-S101 testing or NBC Appendix D tabulated ratings. Required ratings vary from 45 minutes (suite separations in Part 9 buildings) to 2 hours or more (exit stairways, firewalls). Assemblies must be constructed exactly per the ULC listed design.

Firestop systems at penetrations

Per NBC 3.1.9, all penetrations through fire separations must be sealed with firestop systems tested and listed per CAN/ULC-S115. The firestop must match the F-rating (flame) and T-rating (temperature) of the assembly being penetrated. Each firestop installation must correspond to a specific ULC system number for the penetration type, size, and annular space.

Fire door assemblies

Per NBC 3.1.8, closures (fire doors) in fire separations must have a fire-protection rating not less than that required by NBC Table 3.1.8.4. Fire doors must be tested per CAN/ULC-S104 and bear a permanent label from an accredited certification organization. Door hardware, frames, and glazing must all be rated components of the listed assembly.

Structural fire protection

Per NBC 3.2.2, the fire-resistance rating of the structural system must meet requirements based on building height, area, and occupancy. Steel structural members require applied fire protection (spray-applied fireproofing, intumescent coatings, or encasement) unless the NBC permits unprotected construction. Fireproofing thickness must match the ULC design listing for the required rating.

Fire and smoke dampers

Per NBC 3.1.8.6 and NFPA 80, fire dampers are required where ducts penetrate fire separations. Smoke dampers are required where ducts penetrate smoke barriers. Dampers must be ULC-listed per CAN/ULC-S112 (fire dampers) or CAN/ULC-S112.1 (leakage-rated dampers) and installed per the manufacturer's listed instructions. Access panels must be provided for inspection and maintenance.

Exit and egress fire protection

Per NBC 3.4.4, exit stairways must be enclosed in fire separations with a minimum 1-hour rating for buildings up to 4 storeys and 2-hour rating above 4 storeys. Exit corridors require ratings per NBC 3.3.1. Exit signs must be illuminated per NBC 3.4.5 and connected to emergency power. No combustible storage or penetrations are permitted within exit enclosures.

Fire alarm system integration

Per NBC 3.2.4 and CAN/ULC-S524, buildings requiring a fire alarm system must have all components installed, connected, and verified per the fire alarm system design. The system must be installed per CAN/ULC-S524 (Installation of Fire Alarm Systems) and verified per CAN/ULC-S537 (Verification of Fire Alarm Systems). All devices must be ULC-listed.

Checklist for inspecting fire resistance ratings of building assemblies per NBC Part 3 (Fire Protection, Occupant Safety and Accessibility) and ULC (Underwriters Laboratories of Canada) standards.

Reference Standards

  • NBC Part 3 — Fire protection, occupant safety and accessibility
  • National Fire Code of Canada (NFC)
  • ULC fire resistance directory (fire-rated assemblies)
  • CAN/ULC-S101 — Standard methods of fire endurance tests
  • CAN/ULC-S115 — Standard method of fire tests of firestop systems
  • Tools Needed

  • Flashlight
  • Tape measure
  • Firestop product identification guide
  • Assembly detail drawings and ULC listing reference
  • Digital camera for documentation